TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "F" (THE PHILADELPHIA FIRE PREVENTION CODE)
CHAPTER 16 (Amended)
* * *
F-1602.7 Fire protection equipment: A yard hydrant system
installed in accordance with Section F-516.2 shall be provided for open storage
yards where any part of the storage area is two hundred (200) feet (61 m) or
more from a public street. Portable water fire extinguishers with a minimum 4-A
rating, or two (2) portable fire extinguishers with a minimum 2-A rating each,
protected against freezing where necessary, shall be located within seventy-five
(75) feet (22860 mm) of travel distance to the nearest unit at convenient and
conspicuous sites providing access to the fire extinguishers in open
yards.
* * *