F-2002.6 Portable fire extinguishers: At least one (1)
portable fire extinguisher with a minimum [4-A] rating of 2-A:10-B:C shall be
provided for each two thousand (2,000) square feet (186 m2) or fraction thereof
of floor area. Tents or air-supported structures which have equipment or devices
for cooking or heating of food shall have a minimum of two (2) fire
extinguishers, with one (1) extinguisher located behind the serving area. All
fire extinguishers shall be prominently mounted.
F-2002.7 Heating or air
conditioning devices: Devices designed to heat or air condition tents or
air-supported structures are permitted provided that the units and their fuel
and power supplies are located at least twenty (20) feet (6 m) from tents,
air-supported structures and buildings, and ducts do not obstruct exits or
aisles. Flammable and combustible liquid fuels shall be stored at least ten feet
(3 m) from heating units. Barricades shall be provided around heating and air
conditioning devices, their fuel or power supplies and ducts. While the units
are in operation, at least
[27] one trained
person shall monitor their operation. Refueling shall only be performed when a
unit is not in operation. (See Chapter 32 for requirements of flammable and
combustible liquid storage. See Chapter 36 for requirements for liquefied
petroleum gas storage.)
Exception: Electric heaters and air conditioning
units shall be permitted adjacent to the outside of a tent or air-supported
structure provided that the power source is placed at least twenty (20) feet (6
m) from any tent, air-supported structure or building.
F-2002.8 Cooking
and heating of food: Cooking and heating of food shall be performed in a tent
used exclusively for that purpose. The tent shall be at least ten feet (3 m)
from other tents, air-supported structures and buildings. Ovens and ranges
powered by electricity or compressed gas shall be permitted for cooking and
heating of food in tents with the following restrictions:
1. Compressed
gas cylinders shall not exceed forty pounds (18 kg) gas capacity and are limited
to one (1) cylinder per oven or range. The cylinders shall be located outside
and at least five feet (1.5 m) from any tent, air-supported structure, building
or source of ignition.
2. Generators used to power electric ovens and
ranges and the generator's fuel supply shall be located at least twenty
(20) feet (6 m) from tents, air-supported structures and
buildings.
F-2002.9 Smoking: Smoking is not permitted inside a tent or
air-supported structure. "No smoking" signs shall be posted at all entrances and
at conspicuous locations inside.