TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "F" (THE PHILADELPHIA FIRE PREVENTION CODE)
CHAPTER 5 (Amended)
* * *
F-501.1.1 Licensing of Fire Protection Contractors: No
person or organization (hereafter referred as contractor) shall install, repair,
service or test any fire protection system until that contractor is certified,
or employs a person certified in fire protection systems and has obtained a
license to do so and is a licensed and insured Electrical
Contractor.
F-501.1.2 Fire suppression system test permit: Prior to the
testing of any standpipe or automatic fire suppression system a licensed
contractor shall obtain a permit for each test from the Department of Licenses
and Inspections.
Exception: Test permits are not required for portable
fire extinguishers or single cylinder suppression systems installed in
commercial kitchen exhaust hoods.
F-501.1.3 Tagging of equipment: A tag
shall be attached to each automatic fire alarm or fire suppression system which
is installed, repaired or serviced. The tag shall indicate the date of the work
and the name, address and telephone number of the person or company who
performed the work.
F-501.1.4 Notification to the Fire Department of a
fire alarm: The Fire Department shall be notified immediately by the owner,
tenant or occupant of any building and by a central station service of the
activation of any fire alarm signal initiated by manual fire alarm boxes,
automatic fire detectors, waterflow alarms from automatic fire suppression
systems or other fire protection equipment.
F-501.1.5 Changes to fire
protection equipment: When there is a change to any fire protection or emergency
electrical equipment or other building systems that may be used during Fire
Department operations in a building, the Fire Department is to be immediately
notified. Detailed information and instructions on all equipment changes shall
be provided to the Fire Department.
* * *
F-501.3 Acceptance test: All fire protection systems shall be
tested in accordance with the requirements of this code and the building code
listed in Chapter 44. The tests shall be conducted by [the owner or an
authorized representative and in the presence of the code official] a fire
protection systems contractor licensed by the Department of Licenses and
Inspections. Test results shall be listed on approved forms and a copy sent to
the Department of Licenses and Inspections. All tests required by this code and
the standards referenced in this code shall be conducted at the expense of the
owner or the owner's representative.
F-501.4 Periodic test
frequency: Dedicated smoke control systems shall be inspected and operated at
six-month intervals. All other fire protection systems, including emergency
generators in all buildings and all standby and/or emergency electrical systems
in high-rise buildings, shall be tested at not greater than 12-month intervals.
Annual testing and certification of fire protection and emergency electrical
systems shall be performed by a licensed company or
individual.
Exceptions: A licensed contractor is not required
to:
1. Annually test and certify smoke detectors in one and two family
dwellings and single- and multiple-station non-system smoke
detectors.
2. Annually certify tests, inspections and maintenance of
fire protection equipment recommended by equipment manufacturers or national
standards to be performed at times other than annually.
* * *
F-501.4.1.1 Generator sets: A written record of
inspections, tests, exercising, operation and repairs of standby/emergency
generator sets shall be maintained on the premises. The written record shall
include:
1. The date of the maintenance
report,
2. Identification of the servicing personnel,
and
3. Notation of any unsatisfactory condition and the corrective
action taken, including parts replaced.
F-501.4.1.2 Annual
certification: Annual test records and certifications of private fire hydrants,
fire protective signaling systems, fire suppression systems and standby or
emergency electrical systems shall contain the name, address and license number
of the person performing the test and shall be submitted in approved form to the
Commercial and Industrial Fire Inspection Unit of the Department of Licenses and
Inspections.
* * *
F-503.2, F-503.3, F-503.4 and F-503.5 (Delete titles and
text -- substitute as follows)
F-503.2 Fire protective signaling systems:
A fire protective signaling system shall be installed in existing buildings as
required by Sections [1016.4.1] B-917.4.1 through [1016.4.4] B-917.4.5 of the
building code listed in Chapter 44 and in buildings with R-2 Use Groups.
Protective signaling systems required to be installed to comply with this
section shall be installed in accordance with Section [1016.0] B-917.0 of the
building code and NFiPA 72 listed in Chapter
44.
Exceptions:
1. Buildings of Use Group R-2 which do not exceed
three (3) stories are not required to have a fire control panel as part of the
protective signaling system, provided that a secondary power source is provided
for the system.
2. Buildings of Use Group R-2 with a single exit and not
exceeding three (3) stories are not required to have a fire alarm box (manual
pull station) at each story. One (1) fire alarm box is required in the exit at
the exit discharge.
F-503.2.1 Supervision of the System: Fire protective
signaling systems in I Use Groups and high-rise buildings shall be supervised in
accordance with Section [1020.2] B-923.2 of the building code listed in Chapter
44.
Exception: High-rise buildings with local protective signaling
systems which are monitored at constantly attended locations.
F-503.2.2
Manual [F]fire alarm box signage: All manual fire alarm boxes (manual pull
stations) shall have a sign mounted immediately [above] adjacent to the box
which states: "IN CASE OF FIRE: SOUND ALARM AND CALL 911".
Exception:
Where the telephone system in a building does not permit the direct dialing of
911, the sign shall read: "IN CASE OF FIRE: SOUND ALARM AND CALL THE FIRE
DEPARTMENT".
F-503.3 Automatic fire detection: An automatic fire detection
system shall be installed and maintained in full operating condition in the
locations described in Sections F-503.3.1 through F-503.3.4. Automatic fire
detectors shall be smoke detectors, except an approved alternative type of
detector shall be installed in spaces such as boiler rooms where, during normal
operation, products of combustion are present in sufficient quantity to actuate
a smoke detector.
F-503.3.1 I-1 and I-2 Use Groups: All I-1 and I-2 Use
Groups shall have an automatic fire detection system installed throughout the
use group. Automatic fire detection required to be installed to comply with this
section shall be installed in accordance with Section [1017.0] B-918.0 of the
building code and NFiPA 72 listed in Chapter
44.
Exceptions:
1. Hospital patient rooms.
2. Use groups
sprinklered throughout.
F-503.3.2 R-1 and R-2 Use Groups: All R-1 and
R-2 Use Groups shall have an automatic fire detection system as
follows:
F-503.3.2.1 System fire detection: An automatic fire detection
system shall be installed in common areas, corridors and basements. Automatic
fire detection systems required to be installed to comply with this section
shall be installed in accordance with Section [1017.0] B-918.0 of the building
code and NFiPA 72 listed in Chapter 44.
Exception: Buildings sprinklered
throughout.
F-503.3.2.2 Single- and multiple-station smoke detectors:
Single- or multiple-station smoke detectors shall be installed in the following
areas:
1. In each dwelling unit in the immediate vicinity of the
bedrooms and in each story within the dwelling unit, including the
basement.
2. In each bedroom of R-2 Use Groups in high-rise
buildings.
Exception: Buildings sprinklered throughout.
3. In each
guest room of R-1 Use Groups.
4. In each boarding unit, dormitory and
communal sleeping area.
F-503.3.2.2.1 Installation: All single- and
multiple-station smoke detectors shall be installed in accordance with NFiPA 72
listed in Chapter 44 and shall be connected to the primary alternating current
(AC) power source of the building or be wireless systems meeting the
requirements of NFiPA 72 listed in Chapter 44 for such
systems.
F-503.3.2.2.2 Interconnection of detectors: Electrical
interconnection of smoke detectors is required in existing R-2 Use Groups in
high-rise buildings where the sound pressure level of any detector is less than
15 decibels (dBA) above the ambient noise level in any occupied space within the
dwelling unit with intervening doors closed. For the purpose of this section,
the ambient noise level is the greater of the following:
1. The noise
level resulting from the operation of all equipment which is intended for use
during sleeping hours, such as heating and/or cooling units, ceiling fans,
etc.;
2. The noise level resulting from background noise with windows
open; or
3. Thirty-five dBA.
Compliance with this section shall
be within two (2) years of the effective date of this code.
Exception:
Under provisions of prior law (§ 5-3402 of The Philadelphia Code), R-2 Use
Groups located in high-rise buildings shall be in compliance with this section
by 12/17/93.
F-503.3.3 R-3 Use Groups: At least one single- or
multiple-station smoke detector shall be installed in each unit and on each
level, including the basement of each R-3 Use Group. In dwelling units with
split levels, a detector installed in the upper level shall suffice for the
adjacent lower level provided that the lower level is less than one full story
below the upper level and there are not intervening doors between the two
levels. All smoke detectors shall be installed in accordance with Section
[1018.0] B-919.0 of the building code and NFPA 72 listed in Chapter
44.
Exception: In existing R-3 Use Groups, battery powered detectors are
permitted and interconnection of detectors within a dwelling unit is not
required.
F-503.3.3.1 Verification of smoke detectors upon sale of
building: Upon the sale of a building containing R-3 Use Groups the seller shall
certify in writing to the buyer that smoke detectors required by Section
F-503.3.3 have been installed and are in proper operating
condition.
F-503.3.4 Mixed use groups: Where a nonresidential use group
is located below a residential use group, an automatic fire detection system
shall be installed throughout the nonresidential use group. Automatic fire
detection required to be installed to comply with this section shall be
installed in accordance with Section [1017.0] B-918.0 of the building code and
NFiPA 72 listed in Chapter 44.
Exception: Non-residential use groups
sprinklered throughout.
F-503.3.4.1 Fire alarm indicating devices: Fire
alarm indicating devices shall be installed throughout buildings referenced in
Section F-503.3.4 and shall be actuated by all automatic fire detection and
manual fire alarm boxes in the building. Fire alarm indicating devices required
to be installed to comply with this section shall be installed in accordance
with Section [1016.0] B-917.0 of the building code and NFiPA 72 listed in
Chapter 44.
Compliance with this section (F-503.3.4) shall be within one
(1) year of the effective date of this code.
F-503.4 Automatic fire
suppression systems: An automatic fire suppression system shall be installed in
the following buildings or areas of buildings. Except where inappropriate for
the hazard, [S]suppression systems [required to be] which are newly installed to
comply with this section shall be automatic sprinkler systems installed in
accordance with this code, NFPA 13 and the building code.
1. Basements,
classified as windowless stories in accordance with the building code listed in
Chapter 44, which have a floor area exceeding two thousand five hundred (2,500)
square feet (223 m2) and are used for manufacture, sale or
storage.
Exception: R-3 Use Groups.
2. All high-hazard
occupancies and all structures occupied for the manufacture or storage of
articles of cellulose nitrate (pyroxylin) plastic. Vaults located within
buildings for the storage of raw pyroxylin shall be protected with an approved
automatic sprinkler system capable of discharging 1.66 gallons per minute (gpm)
per square foot (0.00113 m3/s . m2) over the area of the
vault.
3. Commercial kitchen exhaust systems in all buildings in
accordance with Section F-309.0.
4. High-rise buildings, whether or not
such buildings (or portions of such buildings) were permitted to omit fire
suppression systems under the terms of any variances granted prior to
12/17/91.
Exception: Portions of high-rise buildings occupied by R-2 Use
Groups.
5. High-rise R-2 Use Group buildings. Suppression systems shall
be located in the following areas of R-2 Use Group high-rise
buildings:
5.1 Basements which are classified as a windowless story in
accordance with the building code listed in Chapter 44.
5.2 Rooms used
for the storage of combustibles when the floor area exceeds one hundred twenty
(120) square feet (11 m2).
5.3 Trash and incinerator chutes and
rooms.
F-503.4.1 Existing dry standpipe risers not exceeding two hundred
seventy-five (275) feet (84 m) in height may be utilized as a means of water
supply for sprinkler systems required by Section F-503.4 provided that all dry
standpipes in the building are interconnected. Pressure and flow requirements
for this combination sprinkler and standpipe system need only satisfy the
sprinkler system requirements in the building code listed in Chapter
44.
F-503.4.2 High-rise buildings required by Section F-503.4.4 to have
fire suppression systems installed shall be in compliance by 12/17/99. The owner
of every high-rise building shall submit to the Department of Licenses and
Inspections for approval a written description of the methods and schedule to be
used to comply with this section or, the owner shall submit notification, on
approved forms, that the building is in compliance with Section F-503.4. Under
provisions of prior law (§ 5-3402 of The Philadelphia Code), such written
description or notification must have been submitted by 12/17/92, and nothing in
this subsection shall be deemed to excuse any failure to have complied with that
deadline. Upon approval of the written description, applications for permits
necessary for compliance shall be submitted to the Department of Licenses and
Inspections in accordance with the following schedule:
1. By 9/17/94,
apply for a permit to install a water supply to all floors of the
building.
2. By 9/17/95, apply for a permit to install fire suppression
on twenty percent (20%) of the floors of the building.
3. By 6/17/96,
apply for a permit to install fire suppression on forty percent (40%) of the
floors of the building.
4. By 3/17/97, apply for a permit to install
fire suppression on sixty percent (60%) of the floors of the
building.
5. By 12/17/97, apply for a permit to install fire suppression
on eighty percent (80%) of the floors of the building.
6. By 9/17/98,
apply for a permit to install fire suppression on one hundred percent (100%) of
the floors of the building.
F-503.4.2.1 Upon notification by the
Department of Licenses and Inspections that a permit review is complete, the
applicant shall obtain the permit within thirty (30) days.
F-503.5
Standpipe systems: Standpipe systems shall be installed in the following
buildings. Standpipe systems required to be installed to comply with this
section shall be installed in accordance with this code and Sections [1012.0]
B-914.0 and [1014.0] B-915.0 of the building code and NFiPA 14 listed in Chapter
44.
1. All buildings having floors used for human occupancy which are
located more than six (6) stories above grade shall have Class I standpipe
systems (fire department use). Existing buildings, without Class I standpipe
systems, which do not exceed two hundred seventy-five (275) feet (84 m) in
height, may install a dry, interconnected standpipe system, without a water
supply.
2. All high-rise buildings where standpipe risers exceed two
hundred seventy-five (275) feet (84 m) from the lowest fire department
connection to the roof or highest connection shall have wet, interconnected
standpipe systems. Dry standpipes with an automatic water supply are permitted
where the system is exposed to freezing temperatures. By 12/17/94 an application
for permit shall be submitted to the Department of Licenses and Inspections for
compliance with this section.
F-503.5.1 Pressure reducing devices:
Pressure reducing devices shall be used on standpipe systems as specified in
Sections F-503.5.1.1 through F-503.5.1.3.
F-503.5.1.1 Class I and Class
III wet standpipe: No pressure restricting or regulating device shall be used at
any Class I or Class III fire department use standpipe hose outlet where the
static or residual water pressure does not exceed one hundred seventy-five (175)
pounds per square inch (1207 kPa). Pressure regulating valves required on Class
I or Class III fire department use standpipe systems shall be adjusted to
provide one hundred seventy-five (175) pounds per square inch (1207 kPa), or as
close to that pressure as the adjustment will permit, without exceeding one
hundred seventy-five (175) pounds per square inch (1207
kPa).
F-503.5.1.2 Class I dry standpipes: No pressure restricting or
regulating device shall be installed on any dry standpipe system having no
permanent water supply.
F-503.5.1.3 Class II standpipes: Building
occupant use 1-½ inch (38 mm) hose outlets on Class II and Class III
standpipe systems shall be equipped with pressure restricting or regulating
devices where the residual pressure at an outlet exceeds one hundred (100)
pounds per square inch (689.5 kPa).
* * *
F-506.1.1 Dry pipe valves: A full flow test shall be
required in 1996 and every three (3) years thereafter, except those protecting
areas which are constantly maintained below a freezing
temperature.
F-506.1.2 Standpipe pressure reducing valves: Flow tests of
standpipe pressure reducing valves shall be required in 1995 and every five (5)
years thereafter to ensure proper operation and correct
setting.
F-506.1.3 Dry standpipe system test: Hydrostatic tests of dry
standpipe systems and dry portions of wet standpipe systems shall be required in
1995 and every five (5) years thereafter.
F-506.1.4 Standpipe pressure
and flow requirements: All Class I and Class III systems which are newly
installed or existing systems which are required to conform to Section F-503.5
shall be capable of maintaining a residual pressure of at least one hundred
(100) psi (690 kPa) at the top most outlet of each riser while flowing the
quantity of water specified by the building code listed in Chapter
44.
Exception: Where the building is equipped throughout with an
automatic sprinkler system and where the highest floor level is not more than
one hundred fifty (150) feet (45720 mm) above the lowest level of fire
department vehicle access, the water supply is not required to exceed the
requirements of NFiPA 13 listed in Chapter 44.
F-506.1.5 Standpipe hose
outlet connections: All hose outlet connections on Class I and Class III
standpipe systems (those for fire department use) shall have 2-½ inch (64
mm) male National Hose standard thread fittings.
Exception: Buildings
required to comply with this section and Section F-503.5 shall apply to the
Department of Licenses and Inspections for a permit to begin the work by
12/17/94.
* * *
F-507.1 Periodic testing and inspection: All
foam-extinguishing systems shall be maintained, periodically inspected and
tested in accordance with NFiPA 11, 11A and [16] 25 listed in Chapter
44.
* * *
F-512.1 Periodic testing and inspection: All fire
protective signaling systems shall be maintained, periodically inspected and
tested in accordance with NFiPA [71 and] 72 listed in Chapter 44 and Sections
F-512.2 and F-512.3.
* * *
F-513.1 Periodic testing and inspection: All automatic
fire detection systems shall be maintained, periodically inspected and tested in
accordance with NFiPA 72 listed in Chapter 44 and Sections F-513.2 through
F-513.10.
* * *
F-514.1 Periodic testing and inspection: All single- and
multiple-station smoke detectors shall be maintained, periodically inspected and
tested in accordance with NFiPA 72 listed in Chapter 44 and Section
F-514.2.
* * *
F-514.2.1 Responsibility for testing and maintenance of
battery-powered smoke detectors within dwelling units: Occupants shall be
responsible for the weekly testing and battery replacement of battery-powered
smoke detectors within their dwelling units. Owners shall be responsible for the
repair or replacement of any non-operating battery-powered smoke detectors
within dwelling units within three (3) days of written notice.
* * *
F-516.2.1 Fire hydrants: Where any building or part
thereof is constructed two hundred (200) feet (61 m) or more from a public
street, or where an existing building is two hundred (200) feet (61 m) or more
from a public street, the owner shall install fire hydrants and fire service
mains in accordance with this code. Measurements for fire hydrant installations
shall be made along the exterior of a
building.
Exceptions:
1. Existing R-3 Use
Groups.
2. Existing buildings with a total floor area not exceeding
eight hundred (800) square feet (74 m2) and used exclusively as a B Use
Group.
3. Buildings where every portion of the building is within three
hundred (300) feet (91 m) of a fire hydrant.
* * *
F-517.1 Installation: All fire department connections
shall be installed in accordance with this code and the building code listed in
Chapter 44.
F-517.1.1 Connections and threads: All fire department
connections shall have two 2-½ inch (64 mm) female National Hose standard
thread connections.
Exceptions:
1. Dry standpipe systems with
six inch (152 mm) risers shall have three 2-½ inch (64 mm) female National
Hose standard thread connections.
2. Limited area sprinkler systems are
not required to have a fire department connection.
3. Buildings required
to comply with this section and Section F-503.4 or Section F-503.5 shall apply
to the Department of Licenses and Inspections for a permit to begin the work by
12/17/94.
F-517.2 Inspection, testing and maintenance: All fire
department connections shall be periodically inspected, tested and maintained in
accordance with NFiPA 25 listed in Chapter 44. To ensure there is no debris in
the piping of a fire department connection, the check valve clapper shall be
removed and the piping back flushed with water to achieve a full flow through
the fire department connection.
Exception: Inspection utilizing a video
camera and monitor shall be permitted in lieu of backflushing for the piping
between the fire department connection and the check valve. Check valves shall
be inspected and maintained as required by NFPA 25.
* * *
F-517.4 Signs (Delete text -- substitute as
follows)
F-517.4 Signs: At each fire department connection, there shall
be a durable, weather-resistant [metal] sign [with raised or indented letters at
least one inch (25 mm) in height] to indicate the type of system (sprinkler,
standpipe or combined sprinkler and standpipe) and the areas of the building the
connection feeds, if it does not feed the entire system. Where a connection
feeds one zone, the floors or areas within the zone shall be indicated on the
sign. A connection feeding only one standpipe riser shall have a sign indicating
where the riser is located within the building. Lettering indicating the type of
system(s) shall be at least one inch (25 mm) in height. Other information shall
be at least ½-inch (13 mm) in height. Wording of signs shall be approved by
the Fire Department.
* * *
F-518.2 Where required: A portable fire extinguisher shall be
installed and maintained in the following locations in accordance with NFiPA 10
listed in Chapter 44:
1. In all occupancies in Use Groups A-1, A-2, A-3,
E, I-1, I-2, R-1, R-2 and H. In R-2 Use Groups one (1) fire extinguisher, with a
minimum rating of 2-A:10-B:C, shall be acceptable when mounted in each dwelling
unit in lieu of mounting fire extinguishers in the public corridors or
stairways.
Exceptions:
1. R-2 Use Groups sprinklered
throughout.
2. R-2 Use Groups with one (1) means of egress and not
exceeding three (3) stories are required to have one (1) fire extinguisher,
mounted approximately equidistant from all dwelling units within the
building.
* * *