TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)
SECTION M-1006.0 FORCED COMBUSTION AIR SUPPLY
M-1006.1 General: Where all combustion air and dilution
air is provided by a mechanical forced air system, the combustion air and
dilution air shall be supplied at the minimum rate of 1 cubic foot per minute
per 2,400 British thermal units per hour of combined input rating of all the
fuel-burning appliances served. Each of the appliances served shall be
electrically interlocked to the mechanical forced air system so as to prevent
operation of the appliances when the mechanical system is not in operation.
Where combustion air and dilution air is provided by the building's
mechanical ventilation system, the system shall provide the specified
combustion/dilution air rate in addition to the required ventilation
air.