TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)
SECTION M-1008.0 OPENING OBSTRUCTIONS
M-1008.1 General: The required size of openings for
combustion and dilution air shall be based on the net free area of each opening.
The net free area of an opening shall be that specified by the manufacturer of
the opening covering. In the absence of such information, openings covered with
metal louvers shall be deemed to have a net free area of 75 percent of the area
of the opening and openings covered with wood louvers shall be deemed to have a
net free area of 25 percent of the area of the opening.
M-1008.2 Dampered
openings: Where the combustion air openings are provided with volume, smoke or
fire dampers, the dampers shall be electrically interlocked with the firing
cycle of the appliances served, so as to prevent operation of any appliance that
draws combustion and dilution air from the room when any of the dampers are
closed.