TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)
SECTION M-1101.0 GENERAL
M-1101.1 Scope: This chapter shall govern the reduction in
required clearances to combustible materials and combustible assemblies for
chimneys, vents, kitchen exhaust equipment, mechanical appliances, and
mechanical devices and equipment.
M-1101.2 Protective assembly
construction and installation: Reduced clearance protective assemblies,
including structural and support elements, shall be constructed of
noncombustible materials. Spacers utilized to maintain an air space between the
protective assembly and the protected material or assembly shall be
noncombustible. Where a space between the protective assembly and protected
combustible material or assembly is specified, the same space shall be provided
around the edges of the protective assembly and the spacers shall be placed so
as to allow air circulation by convection in such space. Protective assemblies
shall not be placed less than 1 inch (25 mm) from the mechanical appliances,
devices or equipment, regardless of the allowable reduced
clearance.
M-1101.3 Appliances in confined spaces: The clearance
reduction methods specified in Table M-1103.3 shall not be utilized to reduce
the clearance required for appliances installed in confined spaces in accordance
with Section M-405.4.1.