TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)
SECTION M-1103.0 REDUCED CLEARANCES
|
Table M-1103.3
|
||||||||
|---|---|---|---|---|---|---|---|---|
|
Type of protective assembly a,b |
Reduced clearance with protection (inches)a,b
|
|||||||
|
Horizontal combustible assemblies
|
Horizontal combustible assemblies, combustible assemblies
located beneath the heat
|
|||||||
|
Required clearance to combustibles without protection
(inches)a,b
|
Required clearance to combustibles without protection
(inches)a,b
|
|||||||
|
|
36
|
18
|
9
|
6
|
36
|
18
|
9
|
6
|
|
Galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), mounted on 1-inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible assembly |
18
|
9
|
5
|
3
|
12
|
6
|
3
|
3
|
|
Galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), spaced 1 inch off the combustible assembly |
18
|
9
|
5
|
3
|
12
|
6
|
3
|
2
|
|
Two layers of galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage), having a 1-inch airspace between layers, spaced 1 inch off the combustible assembly |
18
|
9
|
5
|
3
|
12
|
6
|
3
|
3
|
|
Two layers of galvanized sheet metal, minimum nominal thickness of 0.024 inch (No. 24 Gage) having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly |
18
|
9
|
5
|
3
|
12
|
6
|
3
|
3
|
|
½-inch inorganic insulating board over 1 inch of fiberglass or mineral wool batt, against the combustible assembly |
24
|
12
|
6
|
4
|
18
|
9
|
5
|
3
|
|
3 ½-inch brick wall, spaced 1 inch off the combustible wall |
--
|
--
|
--
|
--
|
12
|
6
|
6
|
6
|
|
3 ½-inch brick wall, against combustible wall |
--
|
--
|
--
|
--
|
24
|
12
|
6
|
5
|
|
Note a. Mineral wood batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and have a minimum melting point of 1,500 degrees F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 (Btu in. ) sq. ft. hr. degrees F.) or less. Insulation board shall be of noncombustible material. Note b. 1 inch = 25.4 mm; Degrees C. = [(degrees)-32]/1.8; 1 pound per cubic foot = 16.02 kg/m3. |
||||||||