TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)
SECTION M-302.0 DEFINITIONS
* * *
Exhaust air: Air removed from a space to the outside
atmosphere and not to be reused.
Exhaust system: An assembly of
connected ducts, plenums, fittings, registers, grilles, dampers, blowers, fans
and hoods through which air is conducted from the space or spaces and exhausted
to the outside atmosphere.
* * *
Return air system: An assembly of connected ducts,
plenums, fittings, dampers, blowers, fans, registers and grilles through which
air from the space or spaces to be heated or cooled is conducted back to the
supply unit (see also "Supply air system").
* * *
Supply air system: An assembly of connected ducts,
plenums, fittings, dampers, blowers, fans, registers and grilles through which
air, heated or cooled, is conducted from the supply unit to the space or spaces
to be heated or cooled (see also "Return air system").
* * *
M-303.4 Stud and joist spaces - (Delete paragraph in its
entirety as written - substitute as follows)
M-303.4 Stud cavity and
joist space plenums: Stud wall cavities and the spaces between solid floor
joists to be utilized as air plenums shall comply with the following
conditions:
1. Such cavities or spaces shall not be utilized as a plenum
for supply air.
2. Such cavities or spaces shall not be part of a
required fireresistance rated assembly.
3. Stud wall cavities shall not
convey air from more than one floor level.
4. Stud wall cavities and
joist space plenums shall comply with the floor penetration protection
requirements of the building code.
5. Stud wall cavities and joist space
plenums shall be isolated from adjacent concealed spaces by approved
fireblocking as required in the building code.
* * *