TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)
SECTION M-305.0 FLEXIBLE AIR DUCTS [32] AND AIR CONNECTORS
M-305.1 Flexible air ducts: Flexible air ducts, both
metallic and nonmetallic, shall conform to the requirements of UL 181 for Class
0 or Class 1 flexible air ducts, and shall be so identified. Flexible air ducts
shall not be limited in length.
M-305.2 Flexible [duct] air connectors:
Flexible air connectors, both metallic and nonmetallic, shall conform to the
requirements of UL 181 for Class 0 or Class 1 flexible air connectors, and shall
be so identified.
* * *
M-305.3 Penetrations prohibited: Flexible air ducts and
flexible air connectors shall not pass through any wall, floor, ceiling or
fireresistance rated assembly.
M-305.4 Air temperature: The temperature
of air in flexible air ducts or flexible air connectors shall be less than 250
degrees F. (121 degrees C.). Flexible air ducts and air connectors shall be
installed with a minimum clearance to an appliance as specified for the labeled
equipment.
M-305.5 Low-, medium- and high-pressure systems: Flexible air
ducts and flexible air connectors shall be rated for the pressure of the air
distribution system in accordance with Section M-304.5.
M-305.6
Installation: Flexible air ducts and flexible air connectors shall be installed
in accordance with the manufacturer's installation
instructions.
* * *
M-306.3.1 Labeling: Duct insulation shall be labeled by
the manufacturer. The label shall indicate the [insulating] thermal resistance
(R) value at the specified installation thickness, the flame spread rating and
the smoke-developed rating.
* * *
M-307.1 General: An air distribution system shall be
designed and installed to supply the required distribution of air at the
specified static pressure. The installation of an air distribution system shall
not affect the fire protection requirements specified in the building
code.
M-307.1.1 Cutting or notching: A structural member shall not be
cut, notched or pierced [in excess of the limitations specified] except as
provided for in the building code [listed in Chapter 21, unless proven safe by a
structural analysis].
M-307.3 Supports: Ducts shall be supported with
approved hangers at intervals not exceeding 10 feet (3048 mm) or by other
approved duct support systems designed in accordance with the building code.
Flexible and other premanufactured ducts shall be supported in accordance with
the manufacturer's installation instructions.
* * *
M-307.6 Registers, grilles and diffusers: Duct registers,
grilles and diffusers shall be installed in accordance with the
manufacturer's installation instructions. Supply air duct registers,
grilles and diffusers shall [have] be provided with opposed blade damper
assemblies or equivalent volume adjustment.
* * *
M-307.7 [Visual] [d] Duct openings: Duct openings and
branch take-offs in bathrooms, toilet rooms and changing rooms shall prevent
visual observation and "cross-talk" from adjoining rooms.
* * *
M-307.10 Private garage ducts: Where a warm-air space
heating system serves both a dwelling unit and an attached or detached garage,
supply duct outlets in the garage shall be located not less than 6 feet 6 inches
above the garage floor and shall be provided with an approved backdraft damper.
Return air shall not be taken from the garage. Outdoor makeup air shall be
supplied to the return air system at a rate not less than the rate of supply air
to the garage. Volume dampers shall not be installed in outdoor makeup air ducts
or openings.
M-308.1.1 Intake openings: Mechanical and gravity outside
air intake openings shall be located a minimum of 10 feet (3048 mm) from any
hazard or noxious contaminant such as vents, chimneys, plumbing vents, streets,
alleys, parking lots and loading docks except as otherwise specified in this
code. [Where a source of contaminant is located within 10 feet (3048 mm) of an
intake opening, such opening shall be located a minimum of 2 feet (610 mm) below
the contaminant source.]
* * *
M-309.2.2 Return air systems:
* * *
Exception: Smoke detectors are not required in the return
air system where the space served by the air distribution system is protected by
a system of area smoke detectors in accordance with the building code. The area
smoke detectors shall comply with Section M-309.4.
* * *
M-309.2.3 Common supply and return air systems: Where
multiple air handling systems share common supply or return air ducts or plenums
with a combined capacity greater than 2,000 cfm, the supply air system shall be
provided with smoke detectors in accordance with Section M-309.2.1. Where the
combined capacity of such air handling units is greater than 15,000 cfm,
additional smoke detectors shall be installed in the return air system in
accordance with Section M-309.2.2.
* * *
M-311.6.1 Alternative materials: Where the products being
exhausted are detrimental to the duct material required in Section M-311.6,
ducts shall be constructed of alternative materials that are compatible with the
exhaust products in accordance with the manufacturer's
recommendations.
* * *
M-312.2 Vent penetrations: Flexible ducts that vent
clothes dryers shall not penetrate or be located within any fireblocking,
draftstopping or any wall, floor/ceiling or other assembly required by the
building code to be fireresistance rated, unless such duct is constructed of
galvanized steel or aluminum of the thickness specified in Table M-304.1 and the
fireresistance rating is maintained in accordance with the building
code.
M-312.[2] 3 Vent size: The minimum diameter of the vent shall be as
specified by the manufacturer but not less than the diameter of the appliance
outlet.
M-312.[3] 4 Cleanout: Each vertical riser shall be
provided with a means for cleanout.
M-312.[4] 5 Vent materials: Dryer
vent materials shall be of galvanized steel or aluminum of the thickness
specified in Table M-304.1, or of flexible exhaust duct
material.
M-312.[5] 6 Flexible ducts: Flexible ducts, where installed,
shall be installed in accordance with the clothes dryer manufacturer's
installation instructions. [Flexible ducts that vent clothes dryers shall not
penetrate or be located within any firestopping, draftstopping or any wall,
floor/ceiling or other assembly required by the building code listed in Chapter
21 to be fireresistance rated, unless such duct is constructed of galvanized
steel or aluminum of the thickness specified in Table M-304.1 and the
fireresistance rating is maintained in accordance with the building code listed
in Chapter 21.]
M-312.[6] 7 Commercial or multiple installations: Vent
systems for commercial or multiple-dryer installations shall conform to the
requirements of Sections M-312.6.1 through M-312.6.3.
M-312.[6] 7.1
Makeup air: Installations exhausting more than 200 cubic feet per minute (0.09
m3/s) shall be provided with makeup air.
M-312.[6] 7.2 Exhaust fan
motors: Exhaust fan motors installed in vent systems shall be located outside of
the air stream.
M-312.[6] 7.3 Interlock: In multiple installations, the
fan shall operate continuously or be interlocked to operate when any individual
unit is operating.
* * *