SECTION M-702.0 DEFINITIONS


Pressure relief valve: A pressure-actuated valve held closed by a spring or other means and designed to relieve pressure automatically in excess of the device's setting.

* * *

Table M-703.4
HYDRONIC PIPE

Material
Standard


Acrylonitrile butadiene styrene (ABS) plastic pipe
ASTM D1527; ASTM D2282
Brass pipe
ASTM B43
Brass tubing
ASTM B135
Copper or copper-alloy pipe
ASTM B42; ASTM B302
Copper or copper-alloy tubing
(Type K, L or M)
ASTM B75; ASTM B88; ASTM B251
Chlorinated polyvinyl chloride
(CPVC) plastic pipe
ASTM D2846; ASTM F441; ASTM F442
Cross-linked polyethylene/
aluminum/cross-linked
polyethylene (PEX-AL-PEX)
pressure pipe
CSA CAN/CSA-B-137.10
Cross-linked polyethylene
(PEX) tubing
ASTM F876; ASTM F877
Lead pipe
FS WW-P-325B
Polybutylene (PB) plastic pipe
and tubing
ASTM D3309
Polyvinyl chloride (PVC)
plastic pipe
ASTM D1785; ASTM D2241
Steel pipe
ASTM A53; ASTM A106
Steel tubing
ASTM A254

* * *

M-704.3.3 Soldered joints: All joint surfaces shall be cleaned. A[n approved] flux conforming to ASTM B813 shall be applied. The joint shall be soldered with a solder conforming to ASTM B32.

M-704.3.4 Solvent-cemented joints: Joint surfaces shall be clean and free from moisture. An approved primer shall be applied to CPVC and to PVC pipe-joint surfaces. Joints shall be made while the cement is wet. Solvent cement conforming to the following standards shall be applied to all joint surfaces:

1. ASTM D2235 for ABS joints.

2. ASTM F493 for CPVC joints.

3. ASTM D2564 for PVC joints.

[CPVC joints shall be made in accordance with ASTM D2846 listed in Chapter 21.]

Joints shall be made at acceptable ambient temperatures as recommended by the solvent cement manufacturer.

* * *

M-707.1.2 Cutting or notching: A structural member shall not be cut, notched or pierced [in excess of the limitations specified] except as provided for in the building code [listed in Chapter 21, unless proven safe by a structural analysis].

* * *

M-709.1 Where required: Shutoff valves shall be installed in hydronic piping systems in the locations indicated in Sections M-709.1.1 through M-709.1.[6] 7.

M-709.1.1 Heat exchangers: Shutoff valves shall be installed on the supply and return side of every heat exchanger.

Exception: Shutoff valves shall not be required where heat exchangers are: integral with a boiler; or are a component of a manufacturer's boiler and heat exchanger packaged unit and are capable of being isolated from the hydronic system by the supply and return valves.

* * *

M-709.1.7 Zone: Shutoff valves shall be installed at each zone and floor.

M-709.2 Reduced pressure: A pressure relief valve shall be installed on the low-pressure side of a hydronic piping system that has been reduced in pressure. The relief valve shall be set at the maximum pressure of the system design. The valve shall be installed in accordance with Section [M-605.0] M-709.2.1 and M-709.2.2.

M-709.2.1 Approval: All relief valves shall bear the label of an approved agency. Relief valves shall have a minimum rated capacity for the equipment served.

M-709.2.2 Discharge: The relief valve shall discharge by gravity. Relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. The discharge pipe shall be the same diameter as the relief valve output. Relief valves shall not discharge so as to be a hazard, a potential cause of damage or otherwise a nuisance.

M-709.3 Access: Valves concealed within construction shall be provided with access panels.