TITLE 4. THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
SUBCODE "PM" (THE PHILADELPHIA PROPERTY MAINTENANCE CODE)
SECTION PM-505.0 MECHANICAL FACILITIES AND EQUIPMENT
PM-505.1 Maintenance: All mechanical equipment, fireplaces
and solid fuel-burning appliances shall be properly installed and maintained in
a safe working condition, and shall be capable of performing the intended
function.
PM-505.1.1 Cooking and heating equipment: All cooking and
heating equipment, components and accessories in every heating, cooking and
water-heating device shall be maintained free from leaks and
obstructions.
PM-505.1.2 Chimney: All fuel-burning equipment and
appliances shall be connected to an approved chimney or vent.
Exception:
Fuel-burning equipment and appliances which are labeled for unvented
operation.
PM-505.1.3 Clearances: All required clearances to combustible
materials shall be maintained.
PM-505.1.4 Safety controls: All safety
controls for fuel-burning equipment shall be maintained in effective
operation.
PM-505.1.5 Combustion air: A supply of air for complete
combustion of the fuel and for ventilation of the space shall be provided for
the fuel-burning equipment.
PM-505.1.6 Energy conservation devices:
Devices purporting to reduce fuel consumption by attachment to a fuel-burning
appliance, to the fuel supply line thereto, or to the vent outlet or vent piping
therefrom, shall not be installed unless labeled for such purpose and installed
in accordance with the manufacturer's instructions.
PM-505.2
Cooling facilities: At such time as the Department of Public Health declares a
heat emergency, the owner or operator of nursing home and senior citizen
occupancies in Use Group I-2 (Dependent Care Facilities) shall, whenever the
indoor ambient air temperature exceeds 81 degrees F (27 degrees C), supply
mechanical air cooling to every habitable room to maintain a temperature not
exceeding 81 degrees F (27 degrees C).
Exception: Where there are
separate mechanical air cooling facilities for each dwelling or rooming unit,
and such facilities are under the sole control of the occupant of the dwelling
or rooming unit.
PM-505.2.1 Equipment: The cooling equipment in the
facility shall be capable of maintaining an indoor ambient air temperature which
does not exceed 81 degrees F (27 degrees C) based on an outside design
temperature of 100 degrees F (38 degrees C).
PM-505.2.2 Room temperature
measurements: The required room temperature shall be measured three feet (914
mm) above the floor approximately at the center of the room.